Delta Electronics DVP-ES2 DIDO User Manual

This product is a digital input/output module, providing 8 digital inputs and 8 digital outputs, and can be directly mounted on the DIN rail.


Delta Electronics DVP-ES2 DIDO User Manual - cover page
Brand
DVP-ES2
Category
Industrial Robot
Document type
User Manual
Language
English
Pages
21
File format
PDF
File size
940 KB
Published
16 March, 2012
Updated
30 September, 2023
Model
DVP-ES2
MD5 checksum
EAB81160D6039A77E4941221F2CBDE58

About this manual

The DVP-ES2 DIDO is an open‑type digital input/output module designed for use with the DVP-ES2 series PLC. It must be installed in a dust‑free, humidity‑controlled enclosure and secured against unauthorized operation.

The document details power requirements, input and output electrical characteristics, mounting options (direct or DIN‑rail), wiring guidelines, and safety precautions such as grounding and protection circuits.

What's inside

  • Product Profile & Dimension
  • Electrical Specifications
  • I/O Terminal Specifications
  • Installation
  • Wiring
  • Power Supply
  • I/O Point Wiring
  • Safety Wiring
  • DIN‑Rail Mounting

Specifications

AC power supply voltage range (MPU)100 ~ 240 VAC
DC power supply for I/O points24 VDC
Output voltage (Relay output)Below 250 VAC, 30 VDC
Output current (Resistive load)2 A per point (5 A per COM)
Insulation resistance>5 MΩ at 500 VDC
Operating temperature0 °C ~ 55 °C
Storage temperature-25 °C ~ 70 °C
Grounding wire size≥1.6 mm² copper

Frequently asked questions

What AC voltage range should be used for the DVP-ES2 series MPU?

The MPU accepts an AC supply of 100 ~ 240 VAC.

What grounding wire is recommended for the PLC?

A copper grounding wire of at least 1.6 mm² (or larger) should be used.