This product is a digital input/output module, providing 8 digital inputs and 8 digital outputs, and can be directly mounted on the DIN rail.
About this manual
The DVP-ES2 DIDO is an open‑type digital input/output module designed for use with the DVP-ES2 series PLC. It must be installed in a dust‑free, humidity‑controlled enclosure and secured against unauthorized operation.
The document details power requirements, input and output electrical characteristics, mounting options (direct or DIN‑rail), wiring guidelines, and safety precautions such as grounding and protection circuits.
What's inside
- Product Profile & Dimension
- Electrical Specifications
- I/O Terminal Specifications
- Installation
- Wiring
- Power Supply
- I/O Point Wiring
- Safety Wiring
- DIN‑Rail Mounting
Specifications
| AC power supply voltage range (MPU) | 100 ~ 240 VAC |
|---|
| DC power supply for I/O points | 24 VDC |
|---|
| Output voltage (Relay output) | Below 250 VAC, 30 VDC |
|---|
| Output current (Resistive load) | 2 A per point (5 A per COM) |
|---|
| Insulation resistance | >5 MΩ at 500 VDC |
|---|
| Operating temperature | 0 °C ~ 55 °C |
|---|
| Storage temperature | -25 °C ~ 70 °C |
|---|
| Grounding wire size | ≥1.6 mm² copper |
Frequently asked questions
What AC voltage range should be used for the DVP-ES2 series MPU?
The MPU accepts an AC supply of 100 ~ 240 VAC.
What grounding wire is recommended for the PLC?
A copper grounding wire of at least 1.6 mm² (or larger) should be used.