Siemens QFM31 Duct Sensor User Manual

QFM31... is a duct sensor for measuring relative humidity (high precision) and temperature. It uses a capacitive humidity measurement principle, has an operating voltage of AC 24 V or DC 13.5.35 V, and a signal output of DC 0.10 V/4...20 mA, for relative humidity and temperature. It is suitable for HVAC applications with high requirements for relative humidity measurement accuracy and response time, and the measurement range covers the entire humidity range of 0...100%.


Siemens QFM31 Duct Sensor User Manual - cover page
Brand
Siemens
Document type
User Manual
Language
Chinese
Pages
6
File format
PDF
File size
209 KB
Updated
01 October, 2023
Model
QFM31
MD5 checksum
A9CBFC14B0537E16819B7737ED987A65

About this manual

The QFM31 series duct sensors from Siemens are designed for high‑accuracy relative humidity and temperature measurement in HVAC applications. The manual describes the sensor’s capacitive humidity principle, temperature measurement ranges, and the available DC 0‑10 V or 4‑20 mA output signals.

Installation guidelines cover mounting the sensor in the middle of a duct, required clearances from steam humidifiers, wiring recommendations (shielded twisted pair, cable length limits), and safety considerations such as using a SELV transformer and maintaining IP65 protection. This manual is written in Chinese.

What's inside

  • Technical Data
  • Mechanical Design
  • Installation Instructions
  • Wiring Connections
  • Engineering Considerations
  • Operating Climate Conditions

Specifications

Working voltageAC 24 V ±20 % or DC 13.5‑35 V
Humidity measurement range0‑100 % RH
Temperature measurement ranges‑35…+35 °C, 0…50 °C, 0…70 °C
Humidity accuracy±2 % RH
Temperature correlation≤ 0.05 % RH/°C
Time constant≈ 20 s (air flow)
Output signal (humidity)DC 0‑10 V or 4‑20 mA
Output signal (temperature)DC 0‑10 V or 4‑20 mA
IP protection ratingIP65

Frequently asked questions

What are the recommended wiring practices for the sensor?

Use shielded cable, route signal and power lines as twisted pairs, keep cable lengths within the allowed range, and follow EMC guidelines in noisy environments.

Download PDF (209 KB)