E72 indicates overcurrent before the By-pass, which occurs when the time programmed for the acceleration ramp is shorter than the actual acceleration time, the nominal motor current is higher than the current that can be supported by the Soft-Starter, or the motor shaft is locked with the rotor blocked. The manual's first action is: “Power-on. Reset key. Auto-reset. Dlx.”
- Model
- WEG SSW-07
- Display shows
- Overcurrent before the By-pass (E72)
- Type
- Fault code
- Source
- Manual p. 50
What E72 means
Overcurrent before the By-pass p. 50
Common causes
- The time programmed for the acceleration ramp is shorter than the actual acceleration time. p. 50
- Nominal motor current higher than the current that can be supported by the Soft-Starter. p. 50
- Motor shaft is locked, rotor blocked. p. 50
What to do
- Power-on. Reset key. Auto-reset. Dlx. p. 50
Before you service the product, read the safety instructions in the manual p. 22.
If E72 is still not resolved
- contact the manufacturer or authorized service center p. 6 “Failure to follow these safety instructions may result in personnel injury and/or equipment damage.”