WEG SSW-05 Plus Error E03: Phase Loss

WEG SSW-05 Plus · taken from the manufacturer’s manual, pages cited

Fault codeE03

E03 indicates a phase loss condition in the three-phase network, short-circuit or thyristor fault, or motor not connected. The manual's first action is: “Soft- Starter is in fault condition. The code is flashing.”

Model
WEG SSW-05 Plus
Display shows
Phase Loss (E03)
Type
Fault code
Source
Manual p. 16

What E03 means

Phase Loss p. 22

Common causes

  • Phase fault in the three-phase network p. 22
  • Short-circuit or thyristor fault p. 22
  • Motor is not connected p. 22
  • Motor connection is not correct p. 22
  • Driving problems with the input contactor. p. 22
  • Input fuses are blown. p. 22
  • Incorrect programming of the MotorCurrentTrimpot or P105. p. 22
  • Motor current consumption lower than required for actuation of the phase loss protection. p. 22

What to do

  1. Soft- Starter is in fault condition. The code is flashing. p. 22

If E03 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact WEG service.