Fault codeE65
E65 indicates immediate undercurrent when the programmed current value is much higher than minimum motor operation current, motor at no load, or hydraulic pump operating at no load. The manual lists no action for this code.
- Model
- WEG SSW-05 Plus
- Display shows
- Immediate Undercurrent (E65)
- Type
- Fault code
- Source
- Manual p. 17
What E65 means
Immediate Undercurrent p. 17
Common causes
- Current value programmed in P610 may be much higher than the minimum motor operation current. p. 17
- Motor at no load. p. 17
- In applications with hydraulic pumps, the pump may be operating at no load. p. 17
If E65 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact WEG service.
This page summarises what the manufacturer’s manual says about E65; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with WEG. Found a mistake? Report an error.