Taian Technology S310-201-H1BCD Error OV-C: Voltage too high during operation/decelleration

Motor driver · taken from the manufacturer’s manual, pages cited

Error codeOV-C

Voltage too high during operation/decelleration means deceleration time set too short or load inertia large, or excessive power supply voltage fluctuation. The manual's first action is: “1. Set a longer deceleration time”

Model
Taian Technology S310-201-H1BCD
Display shows
Voltage too high during operation/decelleration (OV-C)
Type
Error code
Source
Manual p. 46

What OV-C means

Voltage too high during operation/decelleration p. 46

Common causes

  • 1. Deceleration time set too short or load inertia large p. 46
  • 2. Excessive power supply voltage fluctuation p. 46

What to do

  1. 1. Set a longer deceleration time p. 46
  2. 2. Add a braking resistor or braking module p. 46
  3. 3. Install a reactor on the power input side p. 46
  4. 4. Increase inverter capacity p. 46

Before you service the product, read the safety instructions in the manual p. 7.

If OV-C is still not resolved

  • Contact Taian Technology regional dealers or company technical personnel for difficult problems. p. 5
    “当您在使用过程中发现疑难问题时,请与台安科技各地区经销商或本公司技术人员 联系”

This page summarises what the manufacturer’s manual says about OV-C; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Taian Technology. Found a mistake? Report an error.