Fault codeA1902
Parameterization for isochronous operation is not permissible. The manual's first action is: “Adapt the bus parameterization Tdp, Ti, To.”
- Model
- Siemens SINAMICS V90, SIMOTICS S-1FL6
- Display shows
- A1902
- Type
- Fault code
- Source
- Manual p. 305
What A1902 means
PROFIdrive: Clock cycle synchronous operation parameterization not permissible p. 305
Common causes
- Parameterization for isochronous operation is not permissible. p. 305
What to do
- Adapt the bus parameterization Tdp, Ti, To. p. 305
- Adapt the sampling time for the current controller or speed controller. p. 305
- Reduce Tdx by using fewer bus participants or shorter telegrams. p. 305
Before you service the product, read the safety instructions in the manual p. 2.
If A1902 is still not resolved
- Contact service / dealer for assistance p. 2 “Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions.”
- Contact service / dealer for assistance p. 13 “NOTICE Property damage due to loose power connections Insufficient tightening torques or vibration can result in loose power connections. This can result in damage due to fire, device defects or malfunctions.”
This page summarises what the manufacturer’s manual says about A1902; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.