Siemens S5-155U CPU 948 Error Codes

95 codes from pages 224–361 of the manual

This is the list of error codes the Siemens manual gives for the S5-155U CPU 948 Siemens S5-155U CPU 948. Find your code below and open it for what the manual says about its causes and what to do.

Error codes from p. 224

CodeWhat it meansPage
QVZIN Timeout error in initialization p. 224
PARIN Parity error in initialization p. 224
BSTKF Wrong block ID p. 224
BSTEF Wrong block delimiter p. 224
UMCG Illegal memory card inserted p. 224
MODUN Content of the memory card too large for the available internal user memory p. 224
FE2S Error on the second interface p. 224
SRAMF System RAM error p. 224
UAFEHL Error in the interrupt condition code word (UAW) p. 224
KDB1 No DB 1 in multiprocessing operation p. 224
KDX0 No DX 0 in multiprocessing operation p. 224
FDB1 Error in DB 1 p. 224
FDX0 Error in DX 0 p. 224
FMODE No IB 0 process interrupts allowed in multiprocessor mode p. 224
FEDBX Error in the STEP 5 operations G DB, GX DX p. 224
QVZNIO QVZ test faulty p. 224
WEFES Collision of software-driven timed interrupts: queue overflow p. 224
DB0UN DB 0 has been changed since the last COLD RESTART. Therefore, no WARM RESTART possible. p. 224
KB Called block not loaded p. 228
KDB Opened data block not loaded p. 228
SUF Substitution error p. 228
STUEB Block stack overflow p. 228
STUEU Interrupt stack overflow p. 228
NAU Power failure in the central controller p. 228
QVZ Timeout p. 228
ADF Addressing error for digital inputs and outputs with process image p. 228
PARE Parity error p. 228
ZYK Cycle monitoring time exceeded p. 228
8E01H Illegal function no. in ACCU-2-L p. 284
8E02H One of the reserved bits (no. 4 to 15) in ACCU 1 is '1' p. 284
8EFFH Incorrect mode (e.g. when the delayed interrupt is to be disabled and DX 0 contains the parameter "process interrupts via IB 0 = on") p. 284
B501H Block does not exist p. 308
B502H Wrong block number p. 308
B503H Wrong block ID p. 308
01H Block called is not loaded p. 359
02H Addressing error p. 359
03H Cycle time error p. 359
04H Substitution error p. 359
05H Timeout distributed peripherals p. 359
06H Timeout user memory p. 359
07H Load/transfer error with data blocks and extended data blocks p. 359
08H Bracket counter overflow p. 359
09H Data block to be opened does not exist p. 359
0AH Error with internal time interrupts/ other interrupts p. 359
0BH Timeout page frame area p. 359
0CH Timeout global communication area p. 359
0DH Timeout in process image updating p. 359
0EH Timeout in IPC flag synchronization error p. 359
0FH Timeout "P"/"O" peripherals p. 359
10H Timeout since interface module (IM 3/IM 4) missing p. 359
11H Parity error in user memory p. 359
12H Timeout process image transfer p. 359
13H Timeout input byte IB 0 p. 359
14H BSTACK overflow p. 359
15H STS operation p. 359
16H RUN/STOP switch set to STOP position p. 359
17H Halt signal from the coordinator p. 359
19H Load/transfer error with L BYT/ BY (process image update) p. 359
1AH Load/transfer error during addressing via the BR register p. 359
1BH I/Os not ready p. 359
1CH Timeout/parity error during initialization p. 359
1DH AUTOMATIC WARM RESTART not possible p. 360
1EH Illegal start-up type p. 360
1FH Load/transfer error during block transfer operation (incorrect memory area boundaries with TNW, TXB, TXW) p. 360
20H Illegal length for G DB/GX DX p. 360
21H DB/DX already exists for G DB/GX DX p. 360
22H Memory space insufficient for G DB/GX DX p. 360
23H Masked system interrupt is coming through p. 360
24H Block function (compress, transfer, input) required in STOP, COLD RESTART p. 360
25H Battery failure; no start-up possible p. 360
26H Change from single to multiprocessor operation prevents a WARM RESTART p. 360
27H STOP caused by STP operation p. 360
28H Continuous ready signal (I/O module defect)) p. 360
29H Error in DB 0 struct. after OVERALL RESET p. 360
30H No DX 0 in multiprocessing p. 360
32H Proc. int. and sys. int. selected simultaneously p. 360
33H Interrupts and mode incompatible p. 360
34H Invalid DX 0 header p. 360
35H Error in DX 0 block ID p. 360
36H Error in DX 0 parameter p. 360
38H No DB 1 in multiprocessing p. 360
39H Invalid DB 1 header p. 360
3AH DB 1 ID set more than once p. 360
3BH DB 1 byte offset without ID p. 360
3CH Peripheral entered in DB 1 is not plugged in p. 361
3DH Offset too big (parameter error) p. 361
3EH Too many offsets p. 361
61H Checksum error in system program code p. 361
62H Checksum error in code of the STEP 5 logic blocks p. 361
63H Address decoder error p. 361
64H Error testing the user memory organized in words p. 361
65H Error testing the user memory organized in bytes p. 361
66H Error testing cycle time monitoring p. 361
67H Error testing the BASP signal p. 361
68H Error testing the hardware clock p. 361

Codes and descriptions are taken from the manufacturer’s manual; page numbers link to the PDF. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.