A0810 on the Siemens MICROMASTER 440 is listed in the manual as: DC Bus Maximum Voltage Vdc-max Controller Not Activated. The manual's first action is: “Check the following: 1. Input supply voltage (P0756) must be within the allowed range. 2. The load must be matched.”
- Model
- Siemens MICROMASTER 440
- Display shows
- DC Bus Maximum Voltage Vdc-max Controller Not Activated (A0810)
- Type
- Alarm code
- Source
- Manual p. 101
What A0810 means
DC Bus Maximum Voltage Vdc-max Controller Not Activated p. 101
Common causes
- The DC bus maximum voltage Vdc-max controller is not activated because the controller cannot keep the DC bus voltage (r0026) within the range specified by (P2172). p. 101
- If the supply voltage (P0210) remains too high, this alarm may occur. p. 101
- If the motor is driven by the load, causing it to operate in regenerative braking mode, this alarm may occur. p. 101
- During a down‑ramp, if the load inertia is especially large, this alarm may occur. p. 101
What to do
- Check the following: 1. Input supply voltage (P0756) must be within the allowed range. 2. The load must be matched. p. 101
Before you service the product, read the safety instructions in the manual p. 7.
If A0810 is still not resolved
This page summarises what the manufacturer’s manual says about A0810; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.