Error codeF01640

PROFiSafe Driver Fault means an error has been detected in the PROFiSafe driver, such as incorrect parameterization or consecutive number errors. The manual's first action is: “Check PROFiSafe parameters.”

Model
Siemens CU240S
Display shows
PROFiSafe Driver Fault (F01640)
Type
Error code
Source
Manual p. 402

What F01640 means

PROFiSafe Driver Fault p. 402

Common causes

  • An error has been detected with the PROFiSafe driver. p. 402
  • • r0949 = 102: A parameterisation error occurred on P1. The parameters received from the bus are not correct. p. 402
  • • r0949 = 103: A consecutive number error occurred on P1. Current PROFiSafe message has a wrong sign of life. p. 402
  • • r0949 = 104: A CRC error occurred on P1. The PROFiSafe message checksum was incorrect. p. 402
  • • r0949 = 105: A watchdog error occurred on P1. PROFiSafe driver timed out. p. 402
  • • r0949 = 106: Fail safe values are active on P1. p. 402
  • • r0949 = 107: PROFiSafe default error on P1. p. 402
  • • r0949 = 202: A parameterisation error occurred on P2. The parameters received from the bus are not correct. p. 402
  • • r0949 = 203: A consecutive number error occurred on P2. Current PROFiSafe message has a wrong sign of life. p. 402
  • • r0949 = 204: A CRC error occurred on P2. The PROFiSafe message checksum was incorrect. p. 402
  • • r0949 = 205: A watchdog error occurred on P2. PROFiSafe driver timed out. p. 402
  • • r0949 = 206: Fail safe values are active on P2. p. 402
  • • r0949 = 207: PROFiSafe default error on P2. p. 402
  • • r0949 = 208: PROFiSafe configuration error on P2. The drive configuration does not match the configuration from the bus. p. 402
  • • Acknowledge PROFiSafe fault. p. 402

What to do

  1. Check PROFiSafe parameters. p. 402
  2. Check all PROFiSafe settings (including your higher level failsafe control system). p. 402

If F01640 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F01640; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.