Error codeOL1
The OL1 indicates acceleration time RCC is too short, V/F setting is improper, or a restart signal is applied to a rotating motor after a short stop. The manual's first action is: “Increase acceleration time RCC.”
- Model
- Schneider Electric ATV 21
- Display shows
- OL1 (OL1)
- Type
- Error code
- Source
- Manual p. 233
What OL1 means
OL1 p. 233
Common causes
- Acceleration time RCC is too short. p. 233
- V/F setting is improper. p. 233
- After a short stop, a restart signal is applied to a rotating motor. p. 233
- A special motor is used (e.g., a small‑diameter motor). p. 233
- Inverter overheating. p. 233
- Acceleration time ACC is too short. p. 233
- V/F setting is improper. p. 233
- After a short stop, a restart signal is applied to a stationary motor. p. 233
- Load is too large. p. 233
What to do
- Increase acceleration time RCC. p. 233
- Adjust V/F parameters. p. 233
- Use F30 (automatic restart) and F302 (firmware control). p. 233
- Adjust frequency control mode selection parameter F3 (set parameter 6 to 1 or 3 for automatic frequency reduction). p. 233
- Increase acceleration time ACC. p. 233
- Adjust small DC injection value F25 (and DC injection time F25C). p. 233
- Check V/F parameter settings. p. 233
- Use F3G1 (automatic restart) and F3G2 (high‑performance control). p. 233
- Use an inverter with a higher rated value. p. 233
Before you service the product, read the safety instructions in the manual p. 8.
If OL1 is still not resolved
This page summarises what the manufacturer’s manual says about OL1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.