Schneider Electric Altivar 71 Error bUF: [DB unit sh. Circuit]

Schneider Electric Altivar 71 · taken from the manufacturer’s manual, pages cited

Fault codebUF

Short-circuit output from braking unit indicates a short-circuit output from the braking unit. The manual's first action is: “Check the wiring of the braking unit and the resistor. Check the braking resistor”

Model
Schneider Electric Altivar 71
Display shows
[DB unit sh. Circuit] (bUF)
Type
Fault code
Source
Manual p. 287

What bUF means

[DB unit sh. Circuit] p. 287

Common causes

  • Short-circuit output from braking unit p. 287
  • Braking unit not connected p. 287

What to do

  1. Check the wiring of the braking unit and the resistor. Check the braking resistor p. 287
  2. The monitoring of this fault must be disabled by the [Brake res. fault Mgt.] (bUb) parameter, page 256 if there is no resistor or braking unit connected to the drive, at and above 55 kW (75 HP) for ATV71...M3X and at and above 90 kW (120 HP) for ATV71...N4. p. 287

Before you service the product, read the safety instructions in the manual p. 16.

If bUF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about bUF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.