Schneider Electric Altivar 61W Error SCF1: [Motor short circuit]

Altivar 61W drive · taken from the manufacturer’s manual, pages cited

Fault codeSCF1

There is a short-circuit or grounding at the drive output. The manual's first action is: “Check the cables connecting the drive to the motor, and the motor insulation Perform the diagnostic tests via the [1.10 DIAGNOSTICS] menu Reduce the switching frequency Connect chokes in series with the motor”

Model
Schneider Electric Altivar 61W
Display shows
[Motor short circuit] (SCF1)
Type
Fault code
Source
Manual p. 76

What SCF1 means

[Motor short circuit] p. 76

Common causes

  • Short-circuit or grounding at the drive output p. 76

What to do

  1. Check the cables connecting the drive to the motor, and the motor insulation Perform the diagnostic tests via the [1.10 DIAGNOSTICS] menu Reduce the switching frequency Connect chokes in series with the motor p. 76

Before you service the product, read the safety instructions in the manual p. 43.

If SCF1 is still not resolved

  • Disconnect all power including external control power p. 44
    “Disconnect all power including external control power that may be present before servicing the drive.”

This page summarises what the manufacturer’s manual says about SCF1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.