Schneider Electric Altivar 61W Error PHF: [Input phase loss]

Altivar 61W drive · taken from the manufacturer’s manual, pages cited

Fault codePHF

Input phase loss happens when the drive is incorrectly supplied, a fuse is blown, one phase fails, or a 3-phase ATV61 is used on a single phase line supply. The manual's first action is: “Check the power connection and the fuses”

Model
Schneider Electric Altivar 61W
Display shows
[Input phase loss] (PHF)
Type
Fault code
Source
Manual p. 79

What PHF means

[Input phase loss] p. 79

Common causes

  • Drive incorrectly supplied or a fuse blown p. 79
  • Failure of one phase p. 79
  • 3-phase ATV61 used on a single phase line supply p. 79
  • Unbalanced load This protection only operates with the drive on load p. 79

What to do

  1. Check the power connection and the fuses p. 79
  2. Use a 3-phase line p. 79
  3. Disable the fault by setting [Input phase loss] (IPL) = [No] (nO) p. 79

Before you service the product, read the safety instructions in the manual p. 43.

If PHF is still not resolved

  • Disconnect all power including external control power p. 44
    “Disconnect all power including external control power that may be present before servicing the drive.”

This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.