Schneider Altivar 61 Error USF: [Undervoltage]

Schneider Altivar 61 · taken from the manufacturer’s manual, pages cited

Fault codeUSF

The USF code indicates undervoltage where the line supply is too low, there is a transient voltage dip, or the pre-charge resistor is damaged. The manual's first action is: “Check the voltage and the parameters of [UNDERTOLTAGE MGT] (USb-), page 198 Replace the pre-charge resistor Inspect/repair the drive”

Model
Schneider Altivar 61
Display shows
[Undervoltage] (USF)
Type
Fault code
Source
Manual p. 245

What USF means

[Undervoltage] p. 245

Common causes

  • Line supply too low Transient voltage dip Damaged pre-charge resistor p. 245

What to do

  1. Check the voltage and the parameters of [UNDERTOLTAGE MGT] (USb-), page 198 Replace the pre-charge resistor Inspect/repair the drive p. 245

Before you service the product, read the safety instructions in the manual p. 10.

If USF is still not resolved

  • Disconnect all power including external control power p. 4
    “Disconnect all power including external control power that may be present before servicing the drive.”

This page summarises what the manufacturer’s manual says about USF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.