The PHF code indicates input phase loss where the drive is incorrectly supplied or a fuse blown, failure of one phase, 3-phase ATV61 used on a single-phase line supply, or unbalanced load. The manual's first action is: “Check the power connection and the fuses. Use a 3-phase line. Disable the fault by [Input phase loss] (IPL) = [No] (nO). (page 195)”
- Model
- Schneider Altivar 61
- Display shows
- [Input phase loss] (PHF)
- Type
- Fault code
- Source
- Manual p. 245
What PHF means
[Input phase loss] p. 245
Common causes
- Drive incorrectly supplied or a fuse blown Failure of one phase 3-phase ATV61 used on a single-phase line supply Unbalanced load This protection only operates with the drive on load p. 245
What to do
- Check the power connection and the fuses. Use a 3-phase line. Disable the fault by [Input phase loss] (IPL) = [No] (nO). (page 195) p. 245
Before you service the product, read the safety instructions in the manual p. 10.
If PHF is still not resolved
- Disconnect all power including external control power p. 4 “Disconnect all power including external control power that may be present before servicing the drive.”
This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.