Schneider Altivar 61 Error CFF: [Incorrect config.]

Schneider Altivar 61 · taken from the manufacturer’s manual, pages cited

Fault codeCFF

Incorrect config. means changed or removed or the current configuration is inconsistent. The manual's first action is: “Check that there are no card errors. In the event of the option card being changed/removed deliberately, see the remarks below”

Model
Schneider Altivar 61
Display shows
[Incorrect config.] (CFF)
Type
Fault code
Source
Manual p. 245

What CFF means

[Incorrect config.] p. 245

Common causes

  • changed or removed p. 245
  • The current configuration is inconsistent p. 245

What to do

  1. Check that there are no card errors. In the event of the option card being changed/removed deliberately, see the remarks below p. 245
  2. Return to factory settings or retrieve the backup configuration, if it is valid (see page 222) p. 245

Before you service the product, read the safety instructions in the manual p. 10.

If CFF is still not resolved

  • Disconnect all power including external control power p. 4
    “Disconnect all power including external control power that may be present before servicing the drive.”

This page summarises what the manufacturer’s manual says about CFF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.