Schneider Altivar 12 Error LJF: IGBT overheat

Altivar 12 variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeLJF

IGBT overheat indicates the drive overheated or IGBT internal temperature is too high according to ambient temperature and load. The manual's first action is: “Check the size of the load/motor/drive.”

Model
Schneider Altivar 12
Display shows
IGBT overheat (LJF)
Type
Fault code
Source
Manual p. 110

What LJF means

IGBT overheat p. 110

Common causes

  • Drive overheated p. 110
  • IGBT internal temperature is too high according to ambient temperature and load p. 110

What to do

  1. Check the size of the load/motor/drive. p. 110
  2. Reduce the Switching frequency SFr page 59. p. 110
  3. Wait for the drive to cool before restarting p. 110

Before you service the product, read the safety instructions in the manual p. 4.

If LJF is still not resolved

  • contact your local Schneider Electric representative p. 5
    “contact your local Schneider Electric representative. Do not repair or operate the drive.”

This page summarises what the manufacturer’s manual says about LJF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.