Omron WS02-PSTC1-E Error its 01

CX-Protocol Operation Manual · taken from the manufacturer’s manual, pages cited

Error codeits 01

The sequence number in the PMCR instruction is invalid or the protocol data is faulty. The manual's first action is: “Set C2 of PMCR instruction to 0000 to 03E7 hexadecimal (000 to 999 decimal). Check if communications sequence number is correct.”

Model
Omron WS02-PSTC1-E
Display shows
its 01
Type
Error code
Source
Manual p. 207

What its 01 means

Sequence number designated in C2 of PMCR instruction is set to a value other than 000 to 3E7 hexadecimal (000 to 999 decimal). Communications sequence number that does not exist in the protocol data is designated. p. 207

Common causes

  • Sequence number designated in C2 of PMCR instruction is set to a value other than 000 to 3E7 hexadecimal (000 to 999 decimal). Communications sequence number that does not exist in the protocol data is designated. p. 207
  • When storing or reading data from I/O area of CPU Unit, designated area range is exceeded. p. 207
  • Protocol data in the PMSU is faulty. p. 207

What to do

  1. Set C2 of PMCR instruction to 0000 to 03E7 hexadecimal (000 to 999 decimal). Check if communications sequence number is correct. p. 207
  2. Designate another area or reduce the send/receive data size. p. 207
  3. Using the CX-Protocol, rewrite the protocol data. p. 207

Before you service the product, read the safety instructions in the manual p. 21.

If its 01 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.

This page summarises what the manufacturer’s manual says about its 01; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.