The sequence number in the PMCR instruction is invalid or the protocol data is faulty. The manual's first action is: “Set C2 of PMCR instruction to 0000 to 03E7 hexadecimal (000 to 999 decimal). Check if communications sequence number is correct.”
- Model
- Omron WS02-PSTC1-E
- Display shows
- its 01
- Type
- Error code
- Source
- Manual p. 207
What its 01 means
Sequence number designated in C2 of PMCR instruction is set to a value other than 000 to 3E7 hexadecimal (000 to 999 decimal). Communications sequence number that does not exist in the protocol data is designated. p. 207
Common causes
- Sequence number designated in C2 of PMCR instruction is set to a value other than 000 to 3E7 hexadecimal (000 to 999 decimal). Communications sequence number that does not exist in the protocol data is designated. p. 207
- When storing or reading data from I/O area of CPU Unit, designated area range is exceeded. p. 207
- Protocol data in the PMSU is faulty. p. 207
What to do
- Set C2 of PMCR instruction to 0000 to 03E7 hexadecimal (000 to 999 decimal). Check if communications sequence number is correct. p. 207
- Designate another area or reduce the send/receive data size. p. 207
- Using the CX-Protocol, rewrite the protocol data. p. 207
Before you service the product, read the safety instructions in the manual p. 21.
If its 01 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.
This page summarises what the manufacturer’s manual says about its 01; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.