Cannot select O1 or O2 when variable type is write because the address is invalid or the protocol data exceeds the PMSU capacity. The manual's first action is: “Select a different address for a Write channel type.”
- Model
- Omron WS02-PSTC1-E
- Display shows
- Can not select O1 or O2 when variable type is write. (C)
- Type
- Error code
- Source
- Manual p. 361
What C means
Can not select O1 or O2 when variable type is write. p. 361
Common causes
- The address O1 or O2 has been selected for a Write channel type. This is not permitted. p. 361
- A negative number has been entered. p. 361
- The protocol data selected for download to the PMSU is in excess of the capacity of the PMSU. p. 361
- Attempting to change PLC settings which CX-Net is active. p. 361
- The current CX-Protocol session has the maximum number of projects open. p. 361
- The selected port is not correctly set up for Protocol Macro operation. p. 361
- The connected PLC does not match the PLC settings. p. 361
- The Repeat count specified is invalid. p. 361
- A Channel Number has been entered for the Repeat Counter that is outside the range for the selected Channel area. p. 361
- A Check Code
entry has been made in the Message Data dialog, but the check code has not been specified for an appropriate entry. p. 361 - Attempting to specify a Length or an effective address that is larger than the data area. p. 361
- Communications have failed. p. 361
- The Contention Send Request Code has not been selected but entered. p. 361
- CX-Protocol could not initialize the communications driver CX-Server and cannot function properly. p. 361
What to do
- Select a different address for a Write channel type. p. 361
- Enter a positive number. p. 361
- Ensure the Include Source Information option is not set and try again. p. 361
- Close CX-Net and retry. p. 361
- Close one or more projects and try again. p. 361
- Set the port setting to Protocol Macro mode for the selected port. p. 361
- Select a different PLC. p. 361
- Enter a valid value. p. 361
- Enter a valid Channel Number. p. 361
- Specify a Check code area to an entry. p. 361
- Enter valid data. p. 361
- Retry the connection or cancel the dialog and check the PC to PLC communications settings. p. 361
- Check the connection to the PLC and try again. p. 361
- Enter the Contention Send Request. p. 361
- Exit the application and try again. If the failure continues, reboot the computer and try again. If the failure persists, reinstall CX-Protocol. p. 361
Before you service the product, read the safety instructions in the manual p. 21.
If C is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.
This page summarises what the manufacturer’s manual says about C; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.