0376 on the Omron CS1W-CRM21/CJ1W-CRM21 is listed in the manual as: Address duplication error. The manual's first action is: “The duplication error is registered in the error history. All system operations continue. A Slave Unit or Repeater Unit in the same network is set for the same node. Use the following procedure: 1) Turn OFF the power to the Master Unit and the Slave Unit. 2) Change the duplicate node number to a new value. 3) Turn the power back ON to the Master Unit and the Slave Unit.”
- Model
- Omron CS1W-CRM21/CJ1W-CRM21
- Display shows
- Address duplication error (0376)
- Type
- Error code
- Source
- Manual p. 208
What 0376 means
Address duplication error p. 208
Common causes
- An address duplication error was detected for a Slave Unit attempting to participate. p. 208
- 10 hex: Word Input Slave Unit, Word I/O Slave Unit 20 hex: Word Output Slave Unit 40 hex: Bit Input Slave Unit, Bit I/O Slave Unit 50 hex: Bit Output Slave Unit 70 hex: Repeater Unit p. 208
What to do
- The duplication error is registered in the error history. All system operations continue. A Slave Unit or Repeater Unit in the same network is set for the same node. Use the following procedure: 1) Turn OFF the power to the Master Unit and the Slave Unit. 2) Change the duplicate node number to a new value. 3) Turn the power back ON to the Master Unit and the Slave Unit. p. 208
- Node address (hex) p. 208
Before you service the product, read the safety instructions in the manual p. 15.
If 0376 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.
This page summarises what the manufacturer’s manual says about 0376; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.