Omron CS1W-CRM21/CJ1W-CRM21 Error 0378: Illegal configuration error

Omron CS1W-CRM21/CJ1W-CRM21 CompoNet Master Units · taken from the manufacturer’s manual, pages cited

Error code0378

0378 on the Omron CS1W-CRM21/CJ1W-CRM21 is listed in the manual as: Illegal configuration error. The manual's first action is: “Subsequent Slave Unit participation is prohibited from the point where it is detected that the permitted number of Repeater Unit segments has been exceeded in the participation processing. Other system operations continue. The error is registered in the error history. After normal status is restored, the Unit recovers by being restarted. The maximum number of Repeater Unit segments is registered to two in the Master Unit and cannot be changed. This error thus indicates that there are three or more Repeater Unit segments. Correct the wiring and restart the Master Unit.”

Model
Omron CS1W-CRM21/CJ1W-CRM21
Display shows
Illegal configuration error (0378)
Type
Error code
Source
Manual p. 208

What 0378 means

Illegal configuration error p. 208

Common causes

  • It was detected that the Slave Units and Repeater Units requesting to participate in the network exceeded the permitted number of Repeater Unit segments (two). p. 208
  • 10 hex: Word Input Slave Unit, Word I/O Slave Unit 20 hex: Word Output Slave Unit 40 hex: Bit Input Slave Unit, Bit I/O Slave Unit 50 hex: Bit Output Slave Unit 70 hex: Repeater Unit p. 208

What to do

  1. Subsequent Slave Unit participation is prohibited from the point where it is detected that the permitted number of Repeater Unit segments has been exceeded in the participation processing. Other system operations continue. The error is registered in the error history. After normal status is restored, the Unit recovers by being restarted. The maximum number of Repeater Unit segments is registered to two in the Master Unit and cannot be changed. This error thus indicates that there are three or more Repeater Unit segments. Correct the wiring and restart the Master Unit. p. 208
  2. Node address (hex) p. 208

Before you service the product, read the safety instructions in the manual p. 15.

If 0378 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.

This page summarises what the manufacturer’s manual says about 0378; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.