Omron CS1W-CRM21/CJ1W-CRM21 Error HC: Setting table error

Omron CS1W-CRM21/CJ1W-CRM21 CompoNet Master Units · taken from the manufacturer’s manual, pages cited

Error codeHC

A logical error occurred in routing tables read from the CPU Unit at initialization, or a sum error or an error other than a timeout was returned. The manual's first action is: “Correct or delete the routing table.”

Model
Omron CS1W-CRM21/CJ1W-CRM21
Display shows
Setting table error (HC)
Type
Error code
Source
Manual p. 206

What HC means

Setting table error p. 206

Common causes

  • A logical error (such as an out-of-range error) occurred in routing tables read from the CPU Unit at initialization, or a sum error or an error other than a timeout was returned. p. 206

What to do

  1. Correct or delete the routing table. p. 206

Before you service the product, read the safety instructions in the manual p. 15.

If HC is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.