OMRON CS1W-CLK21-V1, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, CQM1H-CLK21, CS1W-RPT01/02/03 Error 26: Command error

Controller Link Unit · taken from the manufacturer’s manual, pages cited

Error code26

Command error means the specified area is not protected, an incorrect password was specified, or the specified area is protected. The manual's first action is: “The program area is not protected, so it isn't necessary to clear protection.”

Model
OMRON CS1W-CLK21-V1, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, CQM1H-CLK21, CS1W-RPT01/02/03
Display shows
Command error (26)
Type
Error code
Source
Manual p. 247

What 26 means

Command error p. 247

Common causes

  • The specified area is not protected. This response code will be returned if an attempt is made to clear protection on an area that is not protected. p. 247
  • An incorrect password has been specified. p. 247
  • The specified area is protected. p. 247
  • To many commands at destination. p. 247
  • The service is being executed. p. 247
  • The service is not being executed. p. 247
  • Service cannot be executed from local node because the local node is not part of the data links. p. 247
  • A buffer error has prevented returning a normal response. p. 247
  • Service cannot be executed because necessary settings haven't been made. p. 247
  • Service cannot be executed because necessary settings haven't been made in the command data. p. 247
  • The specified action or transition number has already been registered. p. 247
  • Cannot clear error because the cause of the error still exists. p. 247

What to do

  1. The program area is not protected, so it isn't necessary to clear protection. p. 247
  2. Specify a password that is registered. p. 247
  3. Execute the command again after executing the PROGRAM AREA PROTECT CLEAR command for the PLC. p. 247
  4. The destination has received more than 5 commands. Either interrupt servicing or wait for servicing to complete before re-executing the command. p. 247
  5. Execute the command again after the service has been completed or aborted. p. 247
  6. Execute the service if necessary. p. 247
  7. Execute the service from a node that is part of the data links. p. 247
  8. Reset the board. If the error persists, replace the board. p. 247
  9. Make the necessary settings. p. 247
  10. Check the command format of and make the necessary settings. p. 247
  11. Execute the command again using an action or transition number that hasn't been registered. p. 247
  12. Eliminate the cause of the error and execute the ERROR CLEAR command. p. 247

Before you service the product, read the safety instructions in the manual p. 13.

If 26 is still not resolved

  • contact your OMRON representative p. 13
    “consult your OMRON representative”