OMRON CS1W-CLK21-V1, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, CQM1H-CLK21, CS1W-RPT01/02/03 Error AR0011

Controller Link Unit · taken from the manufacturer’s manual, pages cited

Error codeAR0011

The same operating level is set twice within the same PLC or a refresh error has occurred between the PLC and the Unit. The manual's first action is: “If two units are required, set them to different operating levels.”

Model
OMRON CS1W-CLK21-V1, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, CQM1H-CLK21, CS1W-RPT01/02/03
Display shows
AR0011
Type
Error code
Source
Manual p. 316

What AR0011 means

The same operating level is set twice within the same PLC. p. 316

Common causes

  • The same operating level is set twice within the same PLC. p. 316
  • A refresh error has occurred between the PLC and the Unit. p. 316

What to do

  1. If two units are required, set them to different operating levels. p. 316
  2. Secure the Controller Link Unit firmly. For C200HX/HG/HE PLCs, tighten the screws on the Bus Connection Unit. If the error occurs even when the Unit is mounted on another PLC, replace the Controller Link Unit. p. 316

Before you service the product, read the safety instructions in the manual p. 13.

If AR0011 is still not resolved

  • contact your OMRON representative p. 13
    “consult your OMRON representative”

This page summarises what the manufacturer’s manual says about AR0011; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with OMRON. Found a mistake? Report an error.