OMRON CS1W-CLK21-V1, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, CQM1H-CLK21, CS1W-RPT01/02/03 Error AR0112

Controller Link Unit · taken from the manufacturer’s manual, pages cited

Error codeAR0112

The routing table data within the DM Area is damaged or there is an error in the routing table setting or a Routing Table Enable Bit (software switch) setting error. The manual's first action is: “Refer to 7-4 Setting Routing Tables and reset correctly. If the error occurs again, replace the Controller Link Unit.”

Model
OMRON CS1W-CLK21-V1, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, CQM1H-CLK21, CS1W-RPT01/02/03
Display shows
AR0112
Type
Error code
Source
Manual p. 316

What AR0112 means

The routing table data within the DM Area is damaged. p. 316

Common causes

  • The routing table data within the DM Area is damaged. p. 316
  • There is an error in the routing table setting or a Routing Table Enable Bit (software switch) setting error. p. 316

What to do

  1. Refer to 7-4 Setting Routing Tables and reset correctly. If the error occurs again, replace the Controller Link Unit. p. 316
  2. When using routing tables refer to 7-4 Setting Routing Tables and reset them correctly. When no routing tables are being used, turn OFF the Routing Table Enable Flag. p. 316

Before you service the product, read the safety instructions in the manual p. 13.

If AR0112 is still not resolved

  • contact your OMRON representative p. 13
    “consult your OMRON representative”

This page summarises what the manufacturer’s manual says about AR0112; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with OMRON. Found a mistake? Report an error.