The routing table data within the DM Area is damaged or there is an error in the routing table setting or a Routing Table Enable Bit (software switch) setting error. The manual's first action is: “Refer to 7-4 Setting Routing Tables and reset correctly. If the error occurs again, replace the Controller Link Unit.”
- Model
- OMRON CS1W-CLK21-V1, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, CQM1H-CLK21, CS1W-RPT01/02/03
- Display shows
- AR0112
- Type
- Error code
- Source
- Manual p. 316
What AR0112 means
The routing table data within the DM Area is damaged. p. 316
Common causes
- The routing table data within the DM Area is damaged. p. 316
- There is an error in the routing table setting or a Routing Table Enable Bit (software switch) setting error. p. 316
What to do
- Refer to 7-4 Setting Routing Tables and reset correctly. If the error occurs again, replace the Controller Link Unit. p. 316
- When using routing tables refer to 7-4 Setting Routing Tables and reset them correctly. When no routing tables are being used, turn OFF the Routing Table Enable Flag. p. 316
Before you service the product, read the safety instructions in the manual p. 13.
If AR0112 is still not resolved
- contact your OMRON representative p. 13 “consult your OMRON representative”
This page summarises what the manufacturer’s manual says about AR0112; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with OMRON. Found a mistake? Report an error.