OL3 means over-torque detection has occurred when output current and/or output torque exceed the over-torque detection values. The manual's first action is: “Check mechanical operating condition, eliminate the cause, or raise the setting to the mechanically allowable value (n098)”
- Model
- Omron 3G3MV
- Display shows
- OL3 (over‑torque detection) (OL3)
- Type
- Error code
- Source
- Manual p. 131
What OL3 means
OL3 (over‑torque detection) p. 131
Common causes
- In V/F mode, inverter output current exceeds over‑torque detection value (n098) p. 131
- In vector mode: output current and output torque exceed over‑torque detection values (n097, n098); when over‑torque is detected, action is taken according to parameter n096 p. 131
What to do
- Check mechanical operating condition, eliminate the cause, or raise the setting to the mechanically allowable value (n098) p. 131
Before you service the product, read the safety instructions in the manual p. 9.
If OL3 is still not resolved
- contact service or dealer p. 6 “请充分熟悉掌握所有机械知识,安全情报注意事项”
This page summarises what the manufacturer’s manual says about OL3; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.