0020h on the IDEC FC5A is listed in the manual as: User Program RAM and Checksum Error. The manual's first action is: “When this error occurs, the user program is automatically written, and timer/counter preset values and extended data register preset values are initialized to the values in the user program. Note that any modified preset values are cleared and restored to their initial values. Clear the error code using the HMI module or WindLDR on a computer.”
- Model
- IDEC FC5A
- Display shows
- User Program RAM and Checksum Error (0020h)
- Type
- Error code
- Source
- Manual p. 413
What 0020h means
User Program RAM and Checksum Error p. 413
Common causes
- Data in the user program write area of the MicroSmart CPU module RAM is corrupted. p. 413
What to do
- When this error occurs, the user program is automatically written, and timer/counter preset values and extended data register preset values are initialized to the values in the user program. Note that any modified preset values are cleared and restored to their initial values. Clear the error code using the HMI module or WindLDR on a computer. p. 413
Before you service the product, read the safety instructions in the manual p. 3.
If 0020h is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact IDEC service.
This page summarises what the manufacturer’s manual says about 0020h; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with IDEC. Found a mistake? Report an error.