0004h on the IDEC FC5A is listed in the manual as: Data Connection Error. The manual's first action is: “To correct this error, correct the function settings and download the user program to each station, or connect the cable correctly. Turn off the slave station power and then turn it back on. Then perform one of the following: • Turn off the master station power and then turn it back on. • Use WindLDR on a computer to initialize the master station data‑connection communication (see page 11‑11). • Activate the master station special internal relay M8007 (data‑connection communication initialization flag) (see page 11‑6).”
- Model
- IDEC FC5A
- Display shows
- Data Connection Error (0004h)
- Type
- Error code
- Source
- Manual p. 412
What 0004h means
Data Connection Error p. 412
Common causes
- This error indicates that the function settings for data‑connection communication are incorrect, or the cable connection is incorrect. Ensure that the slave station number is set to 1–31 using WindLDR. Station numbers must not be duplicated. p. 412
What to do
- To correct this error, correct the function settings and download the user program to each station, or connect the cable correctly. Turn off the slave station power and then turn it back on. Then perform one of the following: • Turn off the master station power and then turn it back on. • Use WindLDR on a computer to initialize the master station data‑connection communication (see page 11‑11). • Activate the master station special internal relay M8007 (data‑connection communication initialization flag) (see page 11‑6). p. 412
Before you service the product, read the safety instructions in the manual p. 3.
If 0004h is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact IDEC service.
This page summarises what the manufacturer’s manual says about 0004h; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with IDEC. Found a mistake? Report an error.