Delta VFD-VE 系列 Error OH2: AC Motor Drive detects heat sink temperature too high, exceeding the protection setpoint (90 °C)

Delta VFD-VE AC motor drive · taken from the manufacturer’s manual, pages cited

Error codeOH2

OH2 indicates the AC Motor Drive has detected a heat sink temperature too high, exceeding the protection setpoint (90 °C). The manual's first action is: “Check if ambient temperature is too high; inspect the heat sink for foreign objects; verify the fan is rotating; ensure the AC motor drive has sufficient ventilation space.”

Model
Delta VFD-VE 系列
Display shows
OH2
Type
Error code
Source
Manual p. 218

What OH2 means

AC Motor Drive detects heat sink temperature too high, exceeding the protection setpoint (90 °C) p. 236

Common causes

  • AC Motor Drive detects heat sink temperature too high, exceeding the protection setpoint (90 °C) p. 236

What to do

  1. Check if ambient temperature is too high; inspect the heat sink for foreign objects; verify the fan is rotating; ensure the AC motor drive has sufficient ventilation space. p. 236

Before you service the product, read the safety instructions in the manual p. 72.

If OH2 is still not resolved

  • Contact local agents for consultation. p. 4
    “若有任 何疑虑的地方请连络本公司各地的代理商洽询,我们的专业人员会乐于为您服务。”

This page summarises what the manufacturer’s manual says about OH2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.