Error codeoL2
This code indicates motor load too large. The manual lists no action for this code.
- Model
- Delta VFD-L
- Display shows
- Motor load too large (oL2)
- Type
- Error code
- Source
- Manual p. 2
What oL2 means
Motor load too large p. 2
Common causes
- Check whether the motor load is excessive p. 2
- Check the over‑torque detection threshold settings (parameters 6‑03 to 6‑05) p. 2
- Check that the wiring between the AC motor drive and motor is secure p. 2
- Check whether the U/T1‑V/T2‑W/T3 output wiring is poorly insulated p. 2
- Increase the acceleration time p. 2
- Decrease the torque boost setting (parameter 7‑02) p. 2
- Replace with a higher‑output‑capacity AC motor drive p. 2
If oL2 is still not resolved
- Contact dealer or distributor for product issues or information discrepancies. p. 1 “如有任何登錄資料與您訂貨資料不符或產品有任何問題,請您與接洽之代理商或經銷商連絡”