Delta VFD-L Error oc: AC motor drive detects abnormal increase of overcurrent on the output side

Delta VFD-L · taken from the manufacturer’s manual, pages cited

Error codeoc

This code indicates the AC motor drive detects abnormal increase of overcurrent on the output side. The manual's first action is: “Inspect the U/T1‑V/T2‑W/T3 connections of the AC motor drive for short circuits”

Model
Delta VFD-L
Display shows
oc
Type
Error code
Source
Manual p. 2

What oc means

AC motor drive detects abnormal increase of overcurrent on the output side p. 2

Common causes

  • Check that the motor rating matches the AC motor drive rating p. 2
  • Check for short circuits or grounding in the motor connections p. 2
  • Check that the wiring between the AC motor drive and motor is secure p. 2
  • Increase the acceleration time (parameters 1‑09, 1‑11) p. 2
  • Check whether the motor is overloaded p. 2

What to do

  1. Inspect the U/T1‑V/T2‑W/T3 connections of the AC motor drive for short circuits p. 2

Before you service the product, read the safety instructions in the manual p. 2.

If oc is still not resolved

  • Contact dealer or distributor for product issues or information discrepancies. p. 1
    “如有任何登錄資料與您訂貨資料不符或產品有任何問題,請您與接洽之代理商或經銷商連絡”