Delta VFD-L Series Error oL2: Motor load too high

Delta VFD-L Series · taken from the manufacturer’s manual, pages cited

Error codeoL2

This code indicates motor load too high. The manual lists no action for this code.

Model
Delta VFD-L Series
Display shows
Motor load too high (oL2)
Type
Error code
Source
Manual p. 2

What oL2 means

Motor load too high p. 2

Common causes

  • Check if the motor load is excessive p. 2
  • Check the over‑torque detection displacement setting values (6-03 ~ 6-05) p. 2
  • Check whether the mounting screws between the AC motor drive and motor are loose p. 2
  • Check whether the LVT1~V/T2-W/T3 output wiring is poorly insulated p. 2
  • Increase acceleration time p. 2
  • Decrease the torque boost setting (7-02) p. 2
  • Replace with a higher-output-capacity AC motor drive p. 2

If oL2 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.