Code 0012 indicates measured value exceeds the alarm limit set by parameter 48.06 Br temp faultlim (brake resistor temperature fault limit). The manual's first action is: “Stop the inverter. Allow the resistor to cool down. Check the brake resistor overload protection settings (parameters 48.01‑48.05). Verify the fault‑limit setting, parameter 48.06 Br temp faultlim (brake resistor temperature fault limit). Ensure the brake cycle meets the allowed limits.”
- Model
- ABB ACS850
- Display shows
- BR OVERHEAT (0x7112) (0012)
- Type
- Fault code
- Source
- Manual p. 291
What 0012 means
BR OVERHEAT (0x7112) p. 291
Common causes
- Measured value exceeds the alarm limit set by parameter 48.06 Br temp faultlim (brake resistor temperature fault limit). p. 291
What to do
- Stop the inverter. Allow the resistor to cool down. Check the brake resistor overload protection settings (parameters 48.01‑48.05). Verify the fault‑limit setting, parameter 48.06 Br temp faultlim (brake resistor temperature fault limit). Ensure the brake cycle meets the allowed limits. p. 291
Before you service the product, read the safety instructions in the manual p. 179.
If 0012 is still not resolved
- 请联系当地的 ABB 代表 p. 296 “请联系当地的 ABB 代表”
This page summarises what the manufacturer’s manual says about 0012; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.