ABB ACS550-02 / ACS550-U2 Error 28: SERIAL 1 ERR

AC drive · taken from the manufacturer’s manual, pages cited

Fault code28

SERIAL 1 ERR means the master system is down, the communication connection is bad, or the time-out selection for the drive is too short. The manual's first action is: “To correct, resolve problem with master system.”

Model
ABB ACS550-02 / ACS550-U2
Display shows
SERIAL 1 ERR (28)
Type
Fault code
Source
Manual p. 230

What 28 means

SERIAL 1 ERR p. 230

Common causes

  • The master system is down. p. 230
  • The communication connection is bad. p. 230
  • The time-out selection for the drive is too short for the given installation. The master is not polling the drive within the specified time-out delay. p. 230
  • Fieldbus communication has timed out. p. 230

What to do

  1. To correct, resolve problem with master system. p. 230
  2. To correct, check communication connection at the drive. p. 230
  3. To correct, increase the time set by parameter 3019 COMM FAULT TIME. p. 230
  4. Check for and correct: * Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). * Communication settings (Group 51: EXT COMM MODULE or Group 53: EFB PROTOCOL as appropriate). * Poor connections and/or noise on line. p. 230

Before you service the product, read the safety instructions in the manual p. 5.

If 28 is still not resolved

  • Contact your local Authorized Service Centre for service. p. 6
    “contact your local Authorized Service Centre for service”

This page summarises what the manufacturer’s manual says about 28; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.