ABB ACS550-02 / ACS550-U2 Error 16: EARTH FAULT

AC drive · taken from the manufacturer’s manual, pages cited

Fault code16

EARTH FAULT means a ground fault detected in the motor or motor cables. The manual's first action is: “if running, the drive coasts to a stop”

Model
ABB ACS550-02 / ACS550-U2
Display shows
EARTH FAULT (16)
Type
Fault code
Source
Manual p. 171

What 16 means

EARTH FAULT p. 171

Common causes

  • Ground faults p. 171
  • Possible ground fault detected in the motor or motor cables. The drive monitors for ground faults while the drive is running and while the drive is not running. Detection is more sensitive when the drive is not running and can produce false positives p. 171
  • A delta grounded input power supply and motor cables with high capacitance may result in erroneous error reports during non-running tests p. 171

What to do

  1. if running, the drive coasts to a stop p. 171
  2. Check for/correct faults in the input wiring. p. 171
  3. Verify that motor cable does not exceed maximum specified length. p. 171
  4. To disable response to fault monitoring when the drive is not running, use parameter 3023 WIRING FAULT. To disable response to all ground fault monitoring, use parameter 3017 EARTH FAULT. p. 171

Before you service the product, read the safety instructions in the manual p. 5.

If 16 is still not resolved

  • Contact your local Authorized Service Centre for service. p. 6
    “contact your local Authorized Service Centre for service”

This page summarises what the manufacturer’s manual says about 16; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.