OUTP WIRING means a possible power wiring error is detected. The manual's first action is: “Check for and correct: * Proper input wiring – line voltage is NOT connected to drive output. * The fault can be erroneously declared if the input power is a delta grounded system and motor cable capacitance is large. This fault can be disabled using parameter 3023 WIRING FAULT.”
- Model
- ABB ACS550-02 / ACS550-U2
- Display shows
- OUTP WIRING (35)
- Type
- Fault code
- Source
- Manual p. 260
What 35 means
OUTP WIRING p. 277
Common causes
- Possible power wiring error detected. When the drive is not running it monitors for an improper connection between the drive input power and the drive output. p. 277
What to do
- Check for and correct: * Proper input wiring – line voltage is NOT connected to drive output. * The fault can be erroneously declared if the input power is a delta grounded system and motor cable capacitance is large. This fault can be disabled using parameter 3023 WIRING FAULT. p. 277
Before you service the product, read the safety instructions in the manual p. 5.
If 35 is still not resolved
- Contact your local Authorized Service Centre for service. p. 6 “contact your local Authorized Service Centre for service”
This page summarises what the manufacturer’s manual says about 35; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.