ABB ACS550-02 / ACS550-U2 Error 35: OUTP WIRING

AC drive · taken from the manufacturer’s manual, pages cited

Fault code35

OUTP WIRING means a possible power wiring error is detected. The manual's first action is: “Check for and correct: * Proper input wiring – line voltage is NOT connected to drive output. * The fault can be erroneously declared if the input power is a delta grounded system and motor cable capacitance is large. This fault can be disabled using parameter 3023 WIRING FAULT.”

Model
ABB ACS550-02 / ACS550-U2
Display shows
OUTP WIRING (35)
Type
Fault code
Source
Manual p. 260

What 35 means

OUTP WIRING p. 277

Common causes

  • Possible power wiring error detected. When the drive is not running it monitors for an improper connection between the drive input power and the drive output. p. 277

What to do

  1. Check for and correct: * Proper input wiring – line voltage is NOT connected to drive output. * The fault can be erroneously declared if the input power is a delta grounded system and motor cable capacitance is large. This fault can be disabled using parameter 3023 WIRING FAULT. p. 277

Before you service the product, read the safety instructions in the manual p. 5.

If 35 is still not resolved

  • Contact your local Authorized Service Centre for service. p. 6