Motor overheating protection activates when the calculated motor temperature exceeds 90 °C, triggering an alarm or fault condition. The manual's first action is: “0 = NOT SEL – No response and/or motor thermal protection not set up. 1 = FAULT – When the calculated motor temperature exceeds 90 °C, displays an alarm (2010, MOTOR TEMP). When the calculated motor temperature exceeds 110 °C, displays a fault (9, MOT OVERTEMP) and the drive coasts to stop. 2 = ALARM – When the calculated motor temperature exceeds 90 °C, displays an alarm (2010, MOTOR TEMP).”
- Model
- ABB ACS550-01 / ACS550-U1
- Display shows
- MOT THERM PROT (3005)
- Type
- Fault code
- Source
- Manual p. 148
What 3005 means
MOT THERM PROT p. 148
Common causes
- Defines the drive response to motor overheating. p. 148
What to do
- 0 = NOT SEL – No response and/or motor thermal protection not set up. 1 = FAULT – When the calculated motor temperature exceeds 90 °C, displays an alarm (2010, MOTOR TEMP). When the calculated motor temperature exceeds 110 °C, displays a fault (9, MOT OVERTEMP) and the drive coasts to stop. 2 = ALARM – When the calculated motor temperature exceeds 90 °C, displays an alarm (2010, MOTOR TEMP). p. 148
Before you service the product, read the safety instructions in the manual p. 6.
If 3005 is still not resolved
- contact your local ABB representative for replacement p. 6 “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
- For more technical information, contact your local ABB representative. p. 7 “For more technical information, contact your local ABB representative.”