PAR PCU 1 indicates inconsistent power control parameters due to improper motor nominal frequency or speed. The manual's first action is: “Check for both of the following: • 1 ≤ (60 · 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED) ≤ 16 • (120 · 9907 MOTOR NOM FREQ / Motor Poles) ≤ 0.992”
- Model
- ABB ACS550-01 / ACS550-U1
- Display shows
- PAR PCU 1 (1009)
- Type
- Fault code
- Source
- Manual p. 246
What 1009 means
PAR PCU 1 p. 265
Common causes
- Parameter values for power control are inconsistent. Improper motor nominal frequency or speed. p. 265
What to do
- Check for both of the following: • 1 ≤ (60 · 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED) ≤ 16 • (120 · 9907 MOTOR NOM FREQ / Motor Poles) ≤ 0.992 p. 265
Before you service the product, read the safety instructions in the manual p. 6.
If 1009 is still not resolved
- contact your local ABB representative for replacement p. 6 “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
- For more technical information, contact your local ABB representative. p. 7 “For more technical information, contact your local ABB representative.”