Fault code1003
PAR AI SCALE indicates inconsistent parameter values for analog input scaling. The manual's first action is: “Check for any of the following: • 1301 MINIMUM A1 > 1302 MAXIMUM A1. • 1304 MINIMUM A2 > 1305 MAXIMUM A2.”
- Model
- ABB ACS550-01 / ACS550-U1
- Display shows
- PAR AI SCALE (1003)
- Type
- Fault code
- Source
- Manual p. 246
What 1003 means
PAR AI SCALE p. 264
Common causes
- Parameter values are inconsistent. p. 264
What to do
- Check for any of the following: • 1301 MINIMUM A1 > 1302 MAXIMUM A1. • 1304 MINIMUM A2 > 1305 MAXIMUM A2. p. 264
Before you service the product, read the safety instructions in the manual p. 6.
If 1003 is still not resolved
- contact your local ABB representative for replacement p. 6 “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
- For more technical information, contact your local ABB representative. p. 7 “For more technical information, contact your local ABB representative.”