Parameter Error indicates a mismatch in parameter settings such as AI1, AI2, or frequency ranges. The manual's first action is: “1. Minimum AI1 > Maximum AI1 (parameters 1301, 1302). 2. Minimum AI2 > Maximum AI2 (parameters 1304, 1305). 3. Minimum frequency > Maximum frequency (parameters 2007, 2008). 4. PFC requires the I/O expansion module (NDIO), but the DDCS parameter settings are incorrect.”
- Model
- ABB ACS400
- Display shows
- Parameter Error (11)
- Type
- Error code
- Source
- Manual p. 152
What 11 means
Parameter Error p. 152
Common causes
- Parameter mismatch: p. 152
What to do
- 1. Minimum AI1 > Maximum AI1 (parameters 1301, 1302). 2. Minimum AI2 > Maximum AI2 (parameters 1304, 1305). 3. Minimum frequency > Maximum frequency (parameters 2007, 2008). 4. PFC requires the I/O expansion module (NDIO), but the DDCS parameter settings are incorrect. p. 152
Before you service the product, read the safety instructions in the manual p. 91.
If 11 is still not resolved