ABB ACA 635 Error INU 2: Short-circuit in parallel connected phase module block 2

IGBT supply section · taken from the manufacturer’s manual, pages cited

Fault codeINU 2

INU 2 means a short-circuit in parallel connected phase module block 2, caused by Par. 9.01 bit 13. The manual's first action is: “Check the fibre optic cables between the NPBU board channel CH1 and the NINT board of phase module block 2.
Check the motor and the motor cable.
Check all power plates in the phase module block 2. If a faulty power plate is detected, replace the whole phase module.”

Model
ABB ACA 635
Display shows
Short-circuit in parallel connected phase module block 2 (INU 2)
Type
Fault code
Source
Manual p. 66

What INU 2 means

Short-circuit in parallel connected phase module block 2 p. 66

Common causes

What to do

  1. Check the fibre optic cables between the NPBU board channel CH1 and the NINT board of phase module block 2.
    Check the motor and the motor cable.
    Check all power plates in the phase module block 2. If a faulty power plate is detected, replace the whole phase module.
    p. 66

Before you service the product, read the safety instructions in the manual p. 6.

If INU 2 is still not resolved

  • contact an ABB service representative p. 61
    “If not, contact an ABB service representative.”

This page summarises what the manufacturer’s manual says about INU 2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.