Fault codeACS 800
ACS 800 indicates excessive IGBT module temperature, with a warning given if the temperature exceeds 115 °C and a trip level of 125 °C. The manual's first action is: “Check ambient conditions”
- Model
- ABB ACA 635
- Display shows
- ACS 800
- Type
- Fault code
- Source
- Manual p. 62
What ACS 800 means
Excessive IGBT module temperature. A warning is given if the temperature exceeds 115 °C. p. 62
Common causes
- Excessive IGBT module temperature. A warning is given if the temperature exceeds 115 °C. p. 62
- Excessive IGBT module temperature. The trip level is 125 °C. p. 62
What to do
- Check ambient conditions p. 62
- Check air flow and fan operation. p. 62
- Check heatsink fins for dust pick-up. p. 62
- Check line current against unit current. p. 62
- Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check line current against unit current. p. 62
Before you service the product, read the safety instructions in the manual p. 6.
If ACS 800 is still not resolved
- contact an ABB service representative p. 61 “If not, contact an ABB service representative.”
This page summarises what the manufacturer’s manual says about ACS 800; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.