Motortronics TE-RTD12 Manuals

ManualLib has 3 documents for the Motortronics TE-RTD12 (Industrial Robot): 3 user manuals. Every file can be read online or downloaded as a PDF for free.

User Manual 3

Key facts

Model
TE-RTD12
Documents
3
Languages
EN
Last added
2023-10-19

Start here

Motortronics TE-RTD12 Relay Device User Manual

Motortronics TE-RTD12 Relay Device User Manual

User Manual 63 pages · 1.5 MB · EN

The Motortronics TE-RTD12 Relay Device is designed to add RTD and differential current monitoring to motor systems. It features 12 RTD inputs, 3 programmable relays, 2 isolated analog inputs, and 1 isolated analog output. The device includes an RS485 port for MODBUS RTU communication and a keypad for programming and monitoring. It can be mounted using a bracket and supports various wiring configurations including 2-, 3-, and 4-wire RTD connections.

Read online

Motortronics TE-RTD12 specifications

Control Voltage110 - 240Vac Nominal 50/60Hz
Inputs12 RTD inputs (Pt100, Ni100, Ni120, Cu10), 3 CT inputs for differential CT’s, 2 isolated 4-20mA inputs, 3 isolated Digital Inputs
Outputs3 programmable form C Relays with 5A contact rating pilot duty, One isolated 4-20mA output
Communication Port2 Wire RS485
ProtocolMODBUS RTU
Operating Temperature32ºF – 122ºF / 0ºC to 50ºC
Storage Temperature-4ºF – 176ºF / -20ºC to 80ºC
Humidity10% to 90% (non-condensing)

Source: Motortronics TE-RTD12 Relay Device User Manual

All Motortronics TE-RTD12 documents by type

User Manual 3

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

How many RTD inputs does the TE-RTD12 have?

It has 12 RTD inputs supporting Pt100, Ni100, Ni120, and Cu10 sensors.

From: Motortronics TE-RTD12 Relay Device User Manual

What communication protocol does the TE-RTD12 use?

It uses MODBUS RTU over a 2-wire RS485 port.

From: Motortronics TE-RTD12 Relay Device User Manual

What is the recommended fuse protection for the input power supply?

Use a fuse protection of 2A 240VAC 5kA RK5 or equivalent fuse.

From: Motortronics TE-RTD12 Relay Device User Manual

Can the device be mounted on a DIN-rail?

Yes, the device can be mounted on a back panel using the mounting bracket or DIN-Rail mount.

From: Motortronics TE-RTD12 Relay Device User Manual

What is the operating temperature range for the TE-RTD12?

The operating temperature range is 32ºF – 122ºF / 0º C to 50ºC.

From: Motortronics TE-RTD12 Relay Device User Manual

How many RTD inputs does the TE-RTD12 have?

The TE-RTD12 has 12 RTD inputs (Pt100, Ni100, Ni120, Cu10).

From: Motortronics TE-RTD12 Relay Device User Manual