Delixi CDI9000 Frequency Converter User Manual
This manual covers the complete lifecycle of the CDI9000 series frequency converters, from safety precautions and acceptance inspection to detailed installation, wiring, and operation procedures. It also explains keyboard functions, parameter configuration, input/output features, and fault diagnosis.
Appendices include technical specifications, optional accessory selection, typical wiring diagrams, and a knowledge Q&A section to help users understand inverter principles and best‑practice troubleshooting. This manual is written in Chinese.
Delixi CDI9000 specifications
| Input Voltage | AC 3‑phase 380 V ±15 % |
|---|---|
| Output Voltage | AC 3‑phase 0‑380 V |
| Output Frequency Range | 0‑300 Hz |
| Power Rating Options | 1.5 kW, 11 kW, 160 kW |
All Delixi CDI9000 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
How do you remove and reinstall the digital operator?
Press the lock tab on the digital operator downward to release it from the front cover, then push it back into the panel; the lock tab will automatically secure it.
What is the recommended input voltage and frequency for the CDI9000‑G1R5T4 model?
The CDI9000‑G1R5T4 model requires an input of AC 3‑phase 380 V ±15 % at 50/60 Hz.
What safety precautions must be observed before powering on the CDI9000?
Only qualified personnel may perform installation and maintenance, the inverter must be fully covered before energizing, and the power must be disconnected for at least 5 minutes to discharge internal capacitors.
When should an AC reactor be installed with the CDI9000?
Install an AC reactor when the power‑to‑inverter capacity ratio exceeds 10:1, when there are thyristor loads or power‑factor correction devices, or when the three‑phase voltage imbalance is greater than 3 %.