Key facts
- Brand
- Dafang Huizhong
- Model
- LCZ-803
- Category
- Other products
- Documents
- 2
- Languages
- ZH
- Last added
- 2023-11-25
Start here

Dafang Huizhong LCZ-803 Series Ultrasonic Flowmeter Installation and Instruction Manual
The LCZ-803 Series ultrasonic flowmeter is made by Tangshan Dafang Huizhong Instrument Co., Ltd. It measures liquid flow in circular pipes using the velocity difference method and uses multipulse technology, digital signal processing, and error correction.
The manual covers the flowmeter introduction, converter installation and connection, converter display and operation, sensor installation and use, cable laying, common fault diagnosis, and RS485 and Modbus communication appendices. It also lists technical specifications and selection codes. This manual is written in Chinese.
Dafang Huizhong LCZ-803 specifications
| Measurement accuracy | Class 1.0 (plug-in) / Class 1.5 (clamp-on) |
|---|---|
| Repeatability | ±0.5% (plug-in) / ±0.8% (clamp-on) |
| Flow velocity range | ±0.3 m/s to ±12.0 m/s |
| Pipe diameter range | 40–2000 mm (plug-in) / 50–2000 mm (clamp-on) |
| Medium temperature | 0°C to 150°C |
| Current output | Optically isolated 4–20 mA, max 500 m, load < 600 Ω |
| Digital communication | RS485, 2400/4800/9600 bps, max 1200 m |
| Power supply | AC 127 V (95–140 V), 50 Hz, ≤10 W |
| Protection rating | IP54 |
| Explosion-proof type | Mining flameproof and intrinsically safe, Exd[ib]I |
| Sensor cable length | Standard 10 m, up to 200 m on order |
| Display | 2×16 graphic backlit LCD |
All Dafang Huizhong LCZ-803 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What media can the LCZ-803 measure?
It measures homogeneous fluids filling the pipe with suspended solids below 10 g/L and particle size below 1 mm, such as tap water, clean water, sewage and industrial wastewater.
What sensor types are available for the LCZ-803?
Two types are available: plug-in sensors for pipe pressure up to 2 MPa, and clamp-on sensors mounted on the pipe outer wall, which have no pressure requirement and suit high-pressure or strongly corrosive fluids.
What measurement principle does the LCZ-803 Series use?
It uses the velocity difference method, based on the difference between ultrasonic propagation times in the upstream and downstream directions.
From: Dafang Huizhong LCZ-803 Series Ultrasonic Flowmeter Installation and Instruction Manual
What liquids can the LCZ-803 Series measure?
It measures homogeneous fluids that fill the pipe, with suspended solids below 10 g/L and particle size below 1 mm, such as tap water, clean water, sewage, and industrial wastewater.
From: Dafang Huizhong LCZ-803 Series Ultrasonic Flowmeter Installation and Instruction Manual