The Copeland CC200 Main Controller Quick Start Guide provides wiring and installation instructions for the CC200 controller and hardware. It covers mounting on DIN rail, power supply wiring, input and output wiring, and specifications for the controller and power supply.
The document also explains stepper valve wiring and supported Sporlan valve settings, expansion module addressing and installation, and the Cold Chain Connect mobile application for setting parameters, graphing inputs and outputs, setting service overrides, and viewing alarms.
Copeland CC200 specifications
| Power Requirement | 24VDC |
|---|---|
| Ambient Operating Temperature | 14°F to 122°F (-10°C to 50°C) |
| Storage Temperature | -40 to 185°F (-40 to 85°C) |
| Relative Humidity | 20-85% RH; non-condensing |
| Mounting | DIN Rail |
| Enclosure Dimensions | 7 3/16” x 4 5/16” x 3” (W x H x D) |
| Primary Power | 120VAC |
| Secondary Power | 24VDC |
| CC200 Power Requirement | 24VDC 60W |
| Required Power Supply | CC200 Power Supply 24VDC 60W, Copeland P/N 318-3183 |
| Wire Spec | 16 AWG or larger diameter wire |
| RS485 Ports | Up to 57.6K Baud; isolated; 150 ohm dipswitch termination |
| ETH1/ETH2 | BACnet TCP/IP repeater (Ethernet 10/100) |
| Bipolar Stepper Output | Up to 500mA/phase; 12 Volt 2-Phase bipolar permanent magnet stepper valves |
| Unipolar Stepper Output | Up to 300mA/phase; 12 Volt 5-wire unipolar permanent magnet stepper valves |
All Copeland CC200 documents by type
The shortest path to a working setup, usually only a few pages.
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What power supply is required for the CC200 Main Controller?
The CC200 requires 24VDC 60W. The listed required power supply is the Copeland CC200 Power Supply 24VDC 60W, P/N 318-3183.
How is the CC200 Main Controller mounted?
It is mounted on a DIN rail.
How many cases can the CC200 coordinate in a lineup?
The CC200 supports seamless coordination of refrigeration case lineups with support for up to 8 cases in a lineup.
From: Copeland CC200 Case Controller and 026-1740 R16 Case Display User Guide
Can the CC200 communicate with a supervisory controller?
Yes, it communicates via BACnet or Modbus and is integrated into the Copeland E2E and E3 supervisory controllers, while running completely stand-alone.