Quick start guide for the Copeland CC200 main controller covering power and input/output wiring, expansion modules, stepper valves, and specifications.
The Copeland CC200 Main Controller Quick Start Guide provides wiring and installation instructions for the CC200 controller and hardware. It covers mounting on DIN rail, power supply wiring, input and output wiring, and specifications for the controller and power supply.
The document also explains stepper valve wiring and supported Sporlan valve settings, expansion module addressing and installation, and the Cold Chain Connect mobile application for setting parameters, graphing inputs and outputs, setting service overrides, and viewing alarms.
| Power Requirement | 24VDC |
|---|---|
| Ambient Operating Temperature | 14°F to 122°F (-10°C to 50°C) |
| Storage Temperature | -40 to 185°F (-40 to 85°C) |
| Relative Humidity | 20-85% RH; non-condensing |
| Mounting | DIN Rail |
| Enclosure Dimensions | 7 3/16” x 4 5/16” x 3” (W x H x D) |
| Primary Power | 120VAC |
| Secondary Power | 24VDC |
| CC200 Power Requirement | 24VDC 60W |
| Required Power Supply | CC200 Power Supply 24VDC 60W, Copeland P/N 318-3183 |
| Wire Spec | 16 AWG or larger diameter wire |
| RS485 Ports | Up to 57.6K Baud; isolated; 150 ohm dipswitch termination |
| ETH1/ETH2 | BACnet TCP/IP repeater (Ethernet 10/100) |
| Bipolar Stepper Output | Up to 500mA/phase; 12 Volt 2-Phase bipolar permanent magnet stepper valves |
| Unipolar Stepper Output | Up to 300mA/phase; 12 Volt 5-wire unipolar permanent magnet stepper valves |
The CC200 requires 24VDC 60W. The listed required power supply is the Copeland CC200 Power Supply 24VDC 60W, P/N 318-3183.
It is mounted on a DIN rail.
Power must be OFF to the CC200 Main Controller before wiring.
It is the CC200 mobile application for setting parameters, graphing inputs and outputs, setting service overrides, and viewing alarms.