Acrel DDSD1352 Manuals

ManualLib has 3 documents for the Acrel DDSD1352: 3 user manuals. Every file can be read online or downloaded as a PDF for free.

User Manual 3

Key facts

Brand
Acrel
Model
DDSD1352
Industry
Industrial
Documents
3
Languages
ZH
Last added
2026-11-08

Start here

Acrel DDSD1352 Single-Phase Electronic Energy Meter User Manual

Acrel DDSD1352 Single-Phase Electronic Energy Meter User Manual

User Manual 14 pages · 380 KB · ZH

DDSD1352 is a single-phase electronic energy meter for low-voltage networks. It measures active energy and electrical parameters such as voltage, current and power, and has infrared communication with optional RS485 communication.

It has an 8-digit LCD, three programmable keys, pulse output and optional time-of-use rates. The meter conforms to GB/T17215.321-2008 and Q31/0114000129C035-2017. This manual is written in Chinese.

Read online

Acrel DDSD1352 specifications

Rated voltageAC 220 V
Reference frequency50 Hz
Voltage input power consumption<10 VA
Basic current10 A
Maximum current60 A
Starting current4‰ of basic current
Current input power consumption<4 VA at maximum current
Measurement accuracyClass 1
Clock accuracyError ≤0.5 s/d
Pulse width80±20 ms
Pulse constant1600 imp/kWh
Dimensions88 mm × 36 mm × 70 mm (2 modules)
Operating temperature-25 to 55 °C
Storage temperature-40 to 70 °C
Humidity≤95% (no condensation)
Altitude<2000 m
Communication interfaceRS485 (A+, B-)
Communication mediumShielded twisted pair
Communication protocolsMODBUS-RTU, DL/T645-07, DL/T645-97
Applicable standardsGB/T17215.321-2008 and Q31/0114000129C035-2017

Source: Acrel DDSD1352 Single-Phase Electronic Energy Meter User Manual

All Acrel DDSD1352 documents by type

Questions answered in these manuals

What electrical parameters can the DDSD1352 measure?

It measures voltage, current, active, reactive and apparent power, power factor and frequency, along with active energy.

From: Acrel DDSD1352 Single-Phase Electronic Energy Meter User Manual

Which communication protocols does the DDSD1352 support?

It supports MODBUS-RTU, DL/T645-07 and DL/T645-97 protocols.

From: Acrel DDSD1352 Single-Phase Electronic Energy Meter User Manual

What auxiliary power voltages does the meter support?

The meter supports DC 48V or AC/DC 85-265V for its auxiliary power supply.

From: 203 DDSD1352 Multi-Circuit Rail-Mounted Multifunctional Energy Meter DTSD1352 Installation and Usage Manual V1.0

What is the rated voltage of the meter?

The rated input voltage is 3×220/380V or 3×380V.

From: 203 DDSD1352 Multi-Circuit Rail-Mounted Multifunctional Energy Meter DTSD1352 Installation and Usage Manual V1.0

What communication protocol does this meter support?

The energy meter uses the MODBUS-RTU protocol for RS485 communication.

From: Acrel DDSD1352 Single-Phase Electronic Energy Meter Installation and User Manual

How many time periods can be configured for tariff rates?

The device supports a configuration of 3 tariffs across 8 time periods.

From: Acrel DDSD1352 Single-Phase Electronic Energy Meter Installation and User Manual