Acrel DDSD1352 Single-Phase Electronic Energy Meter User Manual

Acrel DDSD1352 single-phase electronic energy meter user manual covering installation, operation, display, communication and fault diagnosis.


Acrel DDSD1352 Single-Phase Electronic Energy Meter User Manual - cover page
Brand
Acrel
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
14
File format
PDF
File size
380 KB
Published
08 November, 2026
Updated
08 November, 2026
MD5 checksum
1E1C7E26D5EB1A7C15E5B4D056729E59

About this manual

DDSD1352 is a single-phase electronic energy meter for low-voltage networks. It measures active energy and electrical parameters such as voltage, current and power, and has infrared communication with optional RS485 communication.

It has an 8-digit LCD, three programmable keys, pulse output and optional time-of-use rates. The meter conforms to GB/T17215.321-2008 and Q31/0114000129C035-2017. This manual is written in Chinese.

What's inside

  • Overview
  • Main functions
  • Technical parameters
  • Dimensions
  • Wiring and installation
  • Operation and display
  • Communication
  • Fault diagnosis

Specifications

Rated voltageAC 220 V
Reference frequency50 Hz
Voltage input power consumption<10 VA
Basic current10 A
Maximum current60 A
Starting current4‰ of basic current
Current input power consumption<4 VA at maximum current
Measurement accuracyClass 1
Clock accuracyError ≤0.5 s/d
Pulse width80±20 ms
Pulse constant1600 imp/kWh
Dimensions88 mm × 36 mm × 70 mm (2 modules)
Operating temperature-25 to 55 °C
Storage temperature-40 to 70 °C
Humidity≤95% (no condensation)
Altitude<2000 m
Communication interfaceRS485 (A+, B-)
Communication mediumShielded twisted pair
Communication protocolsMODBUS-RTU, DL/T645-07, DL/T645-97
Applicable standardsGB/T17215.321-2008 and Q31/0114000129C035-2017

Frequently asked questions

What electrical parameters can the DDSD1352 measure?

It measures voltage, current, active, reactive and apparent power, power factor and frequency, along with active energy.

Which communication protocols does the DDSD1352 support?

It supports MODBUS-RTU, DL/T645-07 and DL/T645-97 protocols.

What is the operating temperature range?

The operating temperature range is -25 to 55 °C.

What are the meter dimensions?

The meter dimensions are 88 mm by 36 mm by 70 mm (2 modules).

Download PDF (380 KB)

More Acrel Manuals