Acrel DDSD1352 single-phase electronic energy meter user manual covering installation, operation, display, communication and fault diagnosis.
DDSD1352 is a single-phase electronic energy meter for low-voltage networks. It measures active energy and electrical parameters such as voltage, current and power, and has infrared communication with optional RS485 communication.
It has an 8-digit LCD, three programmable keys, pulse output and optional time-of-use rates. The meter conforms to GB/T17215.321-2008 and Q31/0114000129C035-2017. This manual is written in Chinese.
| Rated voltage | AC 220 V |
|---|---|
| Reference frequency | 50 Hz |
| Voltage input power consumption | <10 VA |
| Basic current | 10 A |
| Maximum current | 60 A |
| Starting current | 4‰ of basic current |
| Current input power consumption | <4 VA at maximum current |
| Measurement accuracy | Class 1 |
| Clock accuracy | Error ≤0.5 s/d |
| Pulse width | 80±20 ms |
| Pulse constant | 1600 imp/kWh |
| Dimensions | 88 mm × 36 mm × 70 mm (2 modules) |
| Operating temperature | -25 to 55 °C |
| Storage temperature | -40 to 70 °C |
| Humidity | ≤95% (no condensation) |
| Altitude | <2000 m |
| Communication interface | RS485 (A+, B-) |
| Communication medium | Shielded twisted pair |
| Communication protocols | MODBUS-RTU, DL/T645-07, DL/T645-97 |
| Applicable standards | GB/T17215.321-2008 and Q31/0114000129C035-2017 |
It measures voltage, current, active, reactive and apparent power, power factor and frequency, along with active energy.
It supports MODBUS-RTU, DL/T645-07 and DL/T645-97 protocols.
The operating temperature range is -25 to 55 °C.
The meter dimensions are 88 mm by 36 mm by 70 mm (2 modules).